PREMIER INDUSTRIES, INC. PREMIERCOOL©
MOTOR: Heavy Duty, Industrial grade, Open face, drip proof sized to meet system requirements.
WET SECTION:WATER DISTRIBUTION: Pump recirculating system with metering valve and bleed off line on pressure side of pump. Water is delivered to PVC schedule 40 header pipe. The water is discharged upwards against a stainless steel water deflector which re-directs the water back evenly onto the full width of the media.
| MODEL NO. | CFM RANGE | CABINET DIMENSIONS | MEDIA DEPTH | PUMP HP | FAN DIA | MOTOR HP @ EXTERNAL STATIC PRESSURE (inches w.g.) | ||||||||||
| WIDTH | HEIGHT | LENGTH | .25" | .50" | .75" | 1.0" | 1.25" | 1.5" | 1.75" | 2.0" | 2.5" | |||||
| PCEC-60 | 4500-6500 | 52" | 41" | 54" | 12" | 1/60 | 18" | 1.0 | 1.5 | 1.5 | 2.0 | 3.0 | 3.0 | 5.0 | 5.0 | 5.0 |
| PCEC-80 | 6500-9500 | 52" | 53" | 60" | 12" | 1/30 | 20" | 2.0 | 2.0 | 3.0 | 3.0 | 5.0 | 5.0 | 5.0 | 7.5 | 7.5 |
| PCEC-120 | 9500-12500 | 62" | 60" | 64" | 12" | 1/30 | 22" | 3.0 | 3.0 | 5.0 | 5.0 | 5.0 | 7.5 | 7.5 | 7.5 | 10.0 |
| PCEC-160 | 12500-16000 | 68" | 67" | 72" | 12" | 1/6 | 25" | 3.0 | 5.0 | 5.0 | 7.5 | 10.0 | 10.0 | 15.0 | 15.0 | 15.0 |
| Note: Inquire with factory for details on accessories. | ||||||||||||||||
Note: CFM is based on delivered air (not nominal or industry standard) at static pressures shown to determine motor horsepower.
INLET TEMPERATURE |
WEB BULB DEPRESSION |
EFFICIENCY % |
TEMP DROP | DISCHARGE TEMP |
||
DRY BULB |
WET BULB |
RH % |
||||
| 54 | 30 | 16 | 90% | 14.4 |
|
|
| 58 | 25 | 22 | 90% | 19.8 |
|
|
| 63 | 20 | 27 | 90% | 24.3 |
|
|
| 66 | 15 | 34 | 90% | 30.6 |
|
|
| 69 | 10 | 41 | 90% | 36.9 |
|
|
| 69 | 5 | 51 | 90% | 45.9 |
|
|
| Note: All temperatures are degrees Fahrenheit. RH% = Percent Relative Humidity. Temp Drop is Dry bulb temperature drop across the cooling media. Discharge Temp is degrees (f) as measured immediately behind the discharge side of the media. | ||||||
Evaporative cooling is effective anytime there is a web bulb depression (difference between dry bulb and wet bulb temperatures). In fact, "dry bulb temperature reduction due to the evaporation of water always results in lower effective temperature regardless of relative humidity level" (1995 ASHRAE handbook, chapter 47, Evaporative cooling)
The PremierCool(c) Commercial Evaporative Cooler is specifically designed for the best economical choice for a high quality, high efficiency evaporative cooler for commercial applications.